Hermesys ChimeraX™ Heavy Industrial Fiber Optic Cable is designed for harsh environments. It features a steel-strength member, SZ stranding, and thermoplastic waterproof tubes for high strength, flexibility, and water resistance. Fire-blocking tapes and LSOH jackets provide excellent fire protection, making it ideal for critical systems in heavy industrial and offshore applications. This ensures reliable performance in tough conditions.
Flame Retardant
IEC 30332-1
IEC 60332-3-24
IEC 61034
Fire Resistance
IEC60331-25
Reference Standard
IEC 60754-1/2
IEC 60794-1-2-E1
IEC 60794-1-2-E3
IEC 60794-1-2-F1
IEC 60794-1-2-F5B
No. of Fibres |
4, 6, 12, 24 |
36, 48, 72 | 96 |
Design (Elements × Fibres per Tube) |
Up to 4×6 |
6×6, 4×12, 6×12 | 8×12 |
Loose Tube / Filler – Ø |
2.1mm |
2.1mm |
2.1mm |
CSM/sheath diameter Nom. |
2.0mm | 2.2mm |
2.0/3.5mm |
Inner sheath thickness (mm) |
1.0 nominal | 1.0 nominal | 1.0 nominal |
Outer sheath thickness Nom. (mm) |
2.0 nominal | 2.0 nominal |
2.0 nominal |
Steel wire braid diameter Nom. |
0.13mm / 85% Density | 0.13mm / 85% Density |
0.13mm / 85% Density |
Cable diameter Nom. (mm) |
18.7 nominal | 20.4nominal | 21.4 nominal |
Cable Weight (kg /km) | 350 | 367 |
390 |
Min. bending radius (mm) |
Without Tension 10 × Cable-Ø |
Under Maximum Tension |
|
Temperature range (°C) |
Installation -10 -> +60; |
Transport. & Storage -40 -> +70 ; |
Operation |
Please refer to our General Installation, Safety & Handling recommendations before handling. |
Characteristics Data | |||
Test | Standard | Value |
Sanction* |
Max. Installation tension |
IEC 60794-1-2-E1 |
3500N |
fibre strain £ 0.33%, Da reversible |
Crush(short term) |
IEC 60794-1-2-E3 |
3500 N / 100mm |
Da £ 0.3 dB(MM), 0.1 dB(SM) |
Temperature range |
IEC 60794-1-2-F1 |
-40 -> +70°C |
Da £ 0.3 dB/km(MM), 0.1 dB/km(SM) |
Water Penetration |
IEC 60794-1-2-F5B |
sample=3m, water=1m |
No water leakage after 24 hour |
* values for single-mode fibers, all-optical measurements performed at 1550 nm.