Hermesys ChimeraX™ series medium to high voltage shielded power cable with a Class 2 stranded copper conductor, TR-XLPE insulation, galvanized steel wire armor, and HDPE anti-termite outer sheath. It offers high dielectric strength, moisture resistance, mechanical protection, and termite resistance, making it suitable for industrial, utility, and underground installations.
Conductor | 3 | Conductor Size | 14.2mm |
Insulation | 3.4mm | Armour (Steel Wire OD) | 2.5 mm |
Overall Diameter (Nom) | 67.5± 5.5 mm | Weight | 10440kg/km |
Conductor DC Resistance (20℃ Max) | 0.124Ω/km | Conductor AC Resistance (90℃ Max) | 0.159Ω/km |
Inductive (60hz) | 0.501 mH/km Trefoil | Capacity (60hz) | 0.353μf/km |
Max. Conductor continuous temperature | 90℃ | Max short circuit temperature of the conductor | 250℃ |
Rated Voltage | 6/10kV | Min. Bend Radius during installation | 20*D |
Min. Bend Radius Set in Position | 12*D | ||
Ampacity A Continuous Current Rating | |||
In-ground direct buried (30℃) | Trefoil 309 | In-ground direct buried (25℃) | Trefoil 319 |
In duct bank (25℃) | Trefoil 284 | In air (40℃) | Trefoil 284 |
Soil Thermal Resistivity: 1.5K.mW: Depth of Burial: 0.8 m (from ground to center of cable) |