Hermesys ChimeraX™ series High-Voltage Power Cable is designed for high-voltage power distribution and is suitable for industrial, underground, and outdoor environments. Its LSOH material, anti-termite, and UV resistance are ideal for safety-sensitive applications. The aluminum armor minimizes weight while providing mechanical protection.
Flame Retardant
IEC 60332-1-1
IEC 60332-1-3
IEC 60332-3-22
Reference Standard
IEC60502-2:2005
Core No. x Cross section | 1 × 150mm² ; 1× 300mm² | Conductor Material | Class 2 circular stranding copper |
Conductor Screen | Semi-conductive compound | Thickness of Conductor Screen (Nom.) | 0.7mm |
Insulation | XLPE | Insulation (Nom.) | 5.5mm |
Insulation Screen | Semi-conductive compound | Thickness of Insulation Screen (Nom.) | 0.6mm |
Thickness of Metallic Screen (Nom.) | 0.12mm | Binder | Flame retardant tape |
Thickness of Binder (Nom.) | 0.2mm | Inner Sheath | Black LSOH |
Thickness of Inner Sheath (Nom.) | 1.2; 1.3mm | Armored Material | AL tape |
No. × Thickness of Armored Layer (Nom.) | 2×0.5mm | Outer Sheath | Black LSOH with Anti-termite UV |
Thickness of Outer Sheath (Nom.) | 4.0mm | Overall Diameter (Nom.) | 41.2; 47.6mm |
Rated voltage | 22kV | Voltage test | The cable shall be subjected to a test voltage of 42kV and held for 5 min, No breakdown shall occur |
Partial discharge test | Partial discharge magnitude shall not exceed 10 pC at 21kV | Max. DC resistance of conductor @20⁰C (Ω/km) | ≤0.124 (1×150mm²) ; 0.0991 (1×300mm²) |
Max. Continuous conductor temp | 90⁰C | ||