Description
Hermesys ChimeraX™ series High-Voltage Power Cable is designed for high-voltage power distribution and is suitable for industrial, underground, and outdoor environments. Its LSOH material, anti-termite, and UV resistance are ideal for safety-sensitive applications. The aluminum armor minimizes weight while providing mechanical protection.
Flame Retardant
IEC 60332-1-1
IEC 60332-1-3
IEC 60332-3-22
Reference Standard
IEC 61034
IEC 60754-1 & 2
IEC60502-2:2005
Specification
| Core No. x Cross section |
1 × 150mm² ; 1× 300mm² |
Conductor Material |
Class 2 circular stranding copper |
| Conductor Screen |
Semi-conductive compound |
Thickness of Conductor Screen (Nom.) |
0.7mm |
| Insulation |
XLPE |
Insulation (Nom.) |
5.5mm |
| Insulation Screen |
Semi-conductive compound |
Thickness of Insulation Screen (Nom.) |
0.6mm |
| Thickness of Metallic Screen (Nom.) |
0.12mm |
Binder |
Flame retardant tape |
| Thickness of Binder (Nom.) |
0.2mm |
Inner Sheath |
Black LSOH |
| Thickness of Inner Sheath (Nom.) |
1.2; 1.3mm |
Armored Material |
AL tape |
| No. × Thickness of Armored Layer (Nom.) |
2×0.5mm |
Outer Sheath |
Black LSOH with Anti-termite UV |
| Thickness of Outer Sheath (Nom.) |
4.0mm |
Overall Diameter (Nom.) |
41.2; 47.6mm |
| Rated voltage |
22kV |
Voltage test |
The cable shall be subjected to a test voltage of 42kV and held for 5 min, No breakdown shall occur |
| Partial discharge test |
Partial discharge magnitude shall not exceed 10 pC at 21kV |
Max. DC resistance of conductor @20⁰C (Ω/km) |
≤0.124 (1×150mm²) ; 0.0991 (1×300mm²) |
| Max. Continuous conductor temp |
90⁰C |
|
|