Hermesys 1728-Core Rollable Ribbon Cable: Up to 1728 Fibres in a 24.8 mm Cable

Data centres and backbone networks need more fibres in less duct space. The Hermesys rollable ribbon cable answers this with rollable ribbon fibre and flexible tube technology, packing up to 1728 fibres into a cable just 24.8 mm across.

Cross-section of Hermesys 1728-core rollable ribbon cable showing 12 colour-coded tubes, two strength members and black PE outer sheath
The Hermesys ultra-high-count ribbon cable uses rollable (spider-web) ribbon fibres in a stranded loose-tube design, reaching up to 1728 fibres.

Rollable Ribbon: More Fibres in Less Space

Rollable (spider-web) ribbon fibres are partially bonded at intervals. This forms a web-like structure that can be rolled and stacked. Fibre density rises sharply, and the corner-fibre problem of standard flat ribbons is avoided.

144 fibres in conventional flat ribbon stack, 7.6 mm diameter
7.6mm
VS
144 fibres in rolled spider-web ribbon, 4.4 mm diameter
4.4mm
144 fibres (density 3.18 fibres/mm²) vs 144 fibres (density 9.48 fibres/mm²)

Hermesys Cable Design Advantages

Fibre Ribbon Design

Partially bonded ribbons roll up in the tube and lay flat for mass fusion splicing. The tube is fully dry and easy to strip, and fibres are tightly packed yet easy to separate.

Flexible Tube

The flexible tube greatly improves bending performance. Its bend radius is only one-fifth of a conventional tube.

Easy Installation

Better bending performance allows installation with a small bend radius, even in tight routes.

The 1728-Core Cable at a Glance

The Hermesys 1728-core ultra-high-count ribbon cable (part of our LadonX™ 288-3456F Rollable Ribbon Fiber Optic Cable range) contains 12 tubes, each holding twelve 12-fibre rollable ribbons. The cable diameter is about 24.8 mm and the weight is 412 kg/km. It withstands a short-term tensile load of 2700 N, with a bend radius of 10D. A non-metallic FRP strength member and a black PE outer sheath complete the design.

We also supply ribbon cables in other fibre counts, constructions and sheaths, such as indoor rollable ribbon cables up to 6912 fibres, central tube designs and CST (corrugated steel tape) armoured ribbon duct cables.

Central tube rollable ribbon cable structure with ribbon fibres, inner sheath, water blocking tape, strength members and outer sheath
Central tube ribbon cable
CST armoured rollable ribbon cable structure with ribbon fibres, inner tube, strength members, corrugated steel tape and outer sheath
CST corrugated steel tape armoured ribbon cable

Colour of Fibres

123456789101112
RedBlueGreenYellowVioletWhiteOrangeGreyBrownBlackAquaPink

Colour of Tubes

123456789101112
RedBlueGreenYellowVioletWhiteOrangeGreyBrownBlackAquaPink

Structure

Cores432576864115214401728
Fibres per Tube12f×1212f×1212f×1212f×1212f×1212f×12
Inner Unit Diameter (mm)4.64.64.64.64.64.6
Cable Diameter (mm, approx.)15.716.819.221.523.324.8
Max Tension (N)270027002700270027002700
Cable Weight (kg/km)181195253309356412
Outer ColourBlackBlackBlackBlackBlackBlack

Technical Specifications

ItemStandardValuePerformance
Attenuation≤0.4 dB/km @1310 nm
≤0.3 dB/km @1550 nm
––
TensileIEC 60794-1-21 E12700 NFibre strain less than 0.6%
CrushIEC 60794-1-21 E31000 N/100 mmΔα ≤ 0.1 dB
ImpactIEC 60794-1-21 E45 N·m, 3 impacts*Δα reversible
TorsionIEC 60794-1-21 E71 m, ±180°Δα ≤ 0.1 dB
Cable BendIEC 60794-1-21 E11R = 10·D
(D: cable diameter)
Δα reversible
Temperature RangeIEC 60794-1-22 F1-30 °C → +70 °C, 12 h, 2 cyclesΔα ≤ 0.15 dB/km
Water PenetrationIEC 60794-1-22 F53 m cable, 1 m water height, 24 hoursNo fluid leaking from the exposed end of the cable

*Additional attenuation after test ≤0.05 dB @1550 nm

Hermesys ultra-high-count cables combine rollable ribbon design with flexible tube technology. They deliver outstanding fibre density, ease of installation and bending performance, and adapt to different applications. Whether for data centres, backbone networks or complex telecom environments, we are committed to providing efficient, reliable and customer-focused fibre solutions.

Need a different fibre count, construction or sheath? Email our team at info@hermesys.com for a quote or technical datasheet.